Online double conversion
Wide input voltage range (110~300Vac)
Input power factor 0.99 (With PFC)
Output power factor 0.9
Maximum charging current 12A (Long run unit)
Charging current can be set by LCD
50Hz/60Hz frequency converter mode
Emergency power off function (EPO)
Eco mode operation for energy saving (ECO)
Generator compatible
SNMP / USB / RS232 multiple communications
Smart battery charging design for optimized battery performance
Selectable output voltage: 200,208,220,230,240Vac
Control Panel
Up to 50 items set by LCD
Battery Cabinets. (Optional)
Technical Specifications:
Phase Single phase with ground
Capacity (VA/Watts)
1000VA / 900W
2000VA / 1800W
3000VA / 2700W
INPUT
Nominal voltage
200/208/220/230/240Vac
Operating voltage range
Lower limit of input voltage
160Vac±5% @100%~80%load
140Vac±5% @80%~70%load
120Vac±5% @70%~60%load 110Vac±5% @60%~0%load (Ambient temp. <35℃)
Lower limit of input voltage
175Vac±5% @100%~80%load
155Vac±5% @80%~70%load
135Vac±5% @70%~60%load 125Vac±5% @60%~0%load (Ambient temp. <35℃)
Upper limit of input voltage
300Vac±5%
Upper comeback voltage from bypass mode to
normal mode
290Vac±5%
Operating frequency range
40~70Hz
Power factor
0.99
Generator input
Support
OUTPUT
Output voltage
200/208/220/230/240Vac
Power factor
0.9
Voltage regulation
±1%
Frequency Bat. mode
Line mode
(Synchronized range)
47~53Hz or 57~63Hz
(50/60±0.1)Hz
Crest factor
3:1
Harmonic distortion (THDv)
≤3% THD with linear load
≤6% THD with non linear load
Waveform
Pure sinewave
Transfer time
AC mode <->Batt. mode
Zero
Inverter <-> Bypass
4ms(Typical)
Efficiency
Line mode
88%
92%
92%
Batt mode
85%
86%
87%
88%
89%
90%
BATTERY
Battery type
12V9AH
Depends on the capacity of external batteries
12V9AH
Depends on the capacity of external batteries
12V9AH
Depends on the capacity of external batteries
Numbers
2
2
3
4
4
6
6
6
8
Backup time
Long run unit depends on the capacity of external batteries
Typical recharging time (Standard modle)
4 hours recover to 90% capacity (Typical)
Charging voltage
27.4Vdc±1%
27.4Vdc ±1%
41.0Vdc±1%
54.7Vdc±1%
54.7Vdc±1%
82.1Vdc±1%
82.1Vdc±1%
82.1Vdc±1%
109.4Vdc±1%
Charging current
1A
12A max,can be set by LCD
1A
12A max,can be set by LCD
1A
12A max,can be set by LCD
SYSTEM FEATURES
Line mode Battery mode
Temp.<40℃
Ambient temp.<35℃
105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal 110%~130%: UPS shuts down after 1minute at battery mode or transfer to bypass when the utility is normal
>130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal
35℃110%:UPS shuts down afte
105%~110%: UPS shuts down after 1 minutes at battery mode or transfer to bypass when the utility is normal
r 3 seconds at battery mode or transfer to bypass when the utility is normal
Short circuit
Hold whole system
Overheat
Line mode: Switch to bypass; Backup mode: Shut down UPS immediately
Battery low
Alarm and switch off
EPO (optional)
Shut down UPS immediately
Audible & Visual alarms
Line failure, Battery low, Over load, System fault
Communication interface
USB + RS232, SNMP card (optional), Relay card (optional)
ENVIRONMENT
Operating temperature
0~40℃
Storage temperature
-25℃~55℃
Humidity range
20~90% RH @ 0~40℃ (Non-condensing)
Altitude
<1500m
Noise level
Less than 50dBA @ 1 Meter
PHYSICAL
Dimension W×H×D (mm)
144×209×293
144×209×293
144×209×293
144×209×399
144×209×399
144×209×399
191×337×460
144×209×399
144×209×399
Net weight (kg)
9.8
4
4.1
17
6.7
6.8
27.6
7.3
7.4
STANDARDS
Safety
IEC/EN62040-1,IEC/EN60950-1
EMC
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8